Chapter 22
Fire resistance
This chapter explains how Statiko verifies the fire resistance of a beam once you have entered its fire design (Chapter 13). Steel follows EN 1993-1-2, with heating under the standard fire and two verification methods. Timber and glulam follow EN 1995-1-2 with the reduced cross-section method. Concrete follows the tabulated data of EN 1992-1-2. Fire is the accidental design situation: it never governs the normal checks, the governing summary or the report's governing check.
Kernel paths in this chapter are under engineering/src/jvmAndAndroidMain/kotlin/statiko/engineering/, except combinations/, which is under engineering/src/commonMain/kotlin/statiko/engineering/. Rules are from spec/beam/fire.md.
Fire actions and combinations
The design effects in fire come from the generated fire combinations, one for each leading variable action, plus a variant with Ginf when wind leads. Each fire combination is verified with its own moments and shears, and the result shows the governing one with its combination identity. You never type Efi,d, and Statiko does not use the ηfi shortcut.
combinations/calculateCombination.kt:68-86Statiko applies ψ1 to the leading variable action and ψ2 to every other variable action, for every design country. The variant with Ginf contains only the permanent load and wind. A beam with fire input but no fire combination reads Unavailable with its reason.
Source: spec/beam/fire.md rules 15 to 19.
Steel: heating in the standard fire
Standard fire curve
eurocode/fire/Iso834StandardFireCurve.kt:5-7Section factor and shadow effect
Am/V is the perimeter of the exposed faces divided by the steel area; [Am/V]b uses the box perimeter. An unprotected member heats with max(Am/V ; 10 m−1) (4.2.5.1(5)). A contour-protected member uses Ap/V = Am/V, and a box-protected member uses [Am/V]b.
eurocode/fire/steel/SteelFireShadowFactor.kt:7-21, eurocode/fire/steel/SteelFireSectionFactor.kt:20-49ksh uses the section's real Am/V, not the floored value.
Thermal properties
eurocode/fire/steel/SteelFireSpecificHeat.kt:10-20ρa = 7850 kg/m³ (3.2.2(1)), and the initial steel temperature is 20 °C unless you change it. With Custom ca and ρa your constant values are used instead.
Unprotected members
eurocode/fire/steel/SteelFireUnprotectedHeatingStep.kt:6-36eurocode/fire/steel/SteelFireUnprotectedHeatingStep.kt:36, eurocode/fire/steel/SteelFireStandardFireHeating.kt:58-95Protected members
eurocode/fire/steel/SteelFireProtectedHeatingStep.kt:41-42eurocode/fire/steel/SteelFireProtectedHeatingStep.kt:43-47Each time step takes θg at the end of the step and ca at the current steel temperature. Intumescent coatings are outside Eq. (4.27) and read Unavailable.
Steel: verification
Reduction factors
ky,θ and kE,θ are interpolated linearly in Table 3.1 (3.2.1(1)):
| θa (°C) | 20–100 | 200 | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 | 1100 | 1200 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ky,θ | 1.000 | 1.000 | 1.000 | 1.000 | 0.780 | 0.470 | 0.230 | 0.110 | 0.060 | 0.040 | 0.020 | 0 |
| kE,θ | 1.000 | 0.900 | 0.800 | 0.700 | 0.600 | 0.310 | 0.130 | 0.090 | 0.0675 | 0.0450 | 0.0225 | 0 |
A zero factor means the section has no resistance, and the check reads Failed.
Source: kernel eurocode/fire/steel/SteelFireYieldReductionFactor.kt:7-19, eurocode/fire/steel/SteelFireElasticModulusReductionFactor.kt:7-19, eurocode/fire/steel/SteelFireReductionTable.kt:4-11.
Critical temperature method
γM,fi = 1.0. Its provenance is "CEN recommended" for Eurocode, "DK NA:2007" for Denmark, and "CEN value · national annex not verified" for Sweden and Serbia. A Custom design country leaves steel fire Unavailable.
eurocode/fire/steel/SteelFireDegreeOfUtilisation.kt:5-16, eurocode/fire/steel/SteelFireModifiedUtilisation.kt:21, eurocode/fire/steel/SteelFireCriticalTemperature.kt:7-13eurocode/fire/steel/SteelFireCriticalTemperature.kt:10-23Rfi,d,0 is the section's resistance in fire at time zero, capped at MRd. κ1 is 0.70 (unprotected) or 0.85 (protected) when a slab covers the top flange and the top face is not exposed, otherwise 1.0. κ2 is 0.85 only at stations over an intermediate support or a fixed end of a statically indeterminate beam with the box ticked, otherwise 1.0. The method passes when θa at the required time is at most θa,cr. Where the beam's restraint does not hold the compressed flange, this method reads Unavailable, because it cannot rule out instability.
Source: kernel eurocode/fire/steel/SteelFireAdaptationFactors.kt:7-23, eurocode/fire/steel/SteelFireMechanicalPartialFactor.kt:5-31, steel/SteelFireBeamResistance.kt:58-74; spec/beam/fire.md rules 21, 25, 27, 28 and 34.
Resistance method
steel/SteelFireBeamResistance.kt:106-170W is plastic for Class 1 and 2 and elastic for Class 3, and the bending resistance is reduced for high shear as in EN 1993-1-1 6.2.8. For lateral-torsional buckling in fire:
eurocode/fire/steel/SteelFireBucklingCurve.kt:8-23, steel/SteelFireBeamResistance.kt:214-244eurocode/fire/steel/SteelFireBucklingCurve.kt:16-17, steel/SteelFireBeamResistance.kt:238-244Mcr is the ambient critical moment of Chapter 17, and the compression flange is taken at the uniform steel temperature. The steel fire verdict is the worse of the two methods. When the critical temperature method is Unavailable for instability, the resistance method gives the verdict.
Torsion in fire
EN 1993-1-2 gives no torsion rule. When the fire combination has torsion, for example from an eccentric load, Statiko verifies it with the normal-temperature rules of Chapter 18 at the steel temperature, as a reading of EN 1993-1-2 4.2.1(2), and the report says so beside the check. The critical temperature method then reads Unavailable and the resistance method gives the verdict, because the critical temperature formula presumes a resistance proportional to ky,θ.
steel/SteelFireBeamTorsionResistance.ktThe torques and the warping moment Mw,Ed are those of the analysis, because E and G drop together; the twist φ grows by 1 / kE,θ and Mcr drops by kE,θ. Shear with torsion uses τfi,Rd as its limit. In the warping interactions My takes Mfi,t,Rd and Mb,fi,t,Rd, while Mz,Rd and the flange resistance Mw,Rd take ky,θ · fy / γM,fi without κ1 and κ2. As at normal temperature, a coexistent shear above half its resistance leaves bending Not supported, and lateral-torsional buckling with torsion is covered for a single span on two pinned or roller supports only.
Timber and glulam: reduced cross-section
eurocode/fire/timber/TimberFireCharringRates.kt:4-17eurocode/fire/timber/TimberFireZeroStrengthLayer.kt:4-12, eurocode/fire/timber/TimberFireEffectiveCharringDepth.kt:5-19Under gypsum plasterboard type A, charring starts at tch = 2.8 · hp − 14 (EN 1995-1-2 (3.11)). From tch to ta = min(2 · tch ; tch + 25 / (2 · βn)) the charring rate is 2 · βn. After ta, dchar = 25 + βn · (t − ta). Under plasterboard k0 = 1.0 throughout, so before tch def = 7 mm with no charring (eurocode/fire/timber/TimberFireEffectiveCharringDepth.kt:58-66). The kernel cites JRC EUR 26698 6.1 for this part.
Source: kernel eurocode/fire/timber/TimberFireCladdingStartTime.kt:4-9, eurocode/fire/timber/TimberFireEffectiveCharringDepth.kt:34-67.
The residual section loses def from each exposed face. Each exposed left or right face reduces the width, and each exposed top or bottom face reduces the depth. A section consumed by charring, or timber with a density below 290 kg/m³, reads Unavailable.
eurocode/fire/timber/TimberFireEffectiveSection.kt:23-26eurocode/fire/timber/TimberFireDesignStrength.kt:4-17, eurocode/fire/timber/TimberFireFractileFactor.kt:4-11, eurocode/fire/timber/TimberFireMechanicalPartialFactor.kt:5-14eurocode/fire/timber/TimberFireBendingStress.kt:11, eurocode/fire/timber/TimberFireShearStress.kt:4-12Lateral-torsional buckling in fire runs for solid timber only; glulam reads Unavailable. Statiko first finds an effective length from the ambient critical moment, then the critical stress of the residual section:
timber/TimberFireLtbEffectiveLength.kt:6-24, eurocode/fire/timber/TimberFireCriticalBendingStress.kt:4-28kcrit then follows the branches of EN 1995-1-1 (6.34) from the relative slenderness λrel,m = √(kfi · fm,k / σm,crit,fi), which the kernel computes with kfi inside the root and for which no clause is cited, and the check is σm,d / (kcrit · fm,d,fi) (eurocode/fire/timber/TimberFireKCrit.kt:5-26, eurocode/fire/timber/TimberFireReducedCrossSectionVerification.kt:166-203). A top flange restrained by a slab makes this check Not evaluated with the timber reason Top flange laterally restrained: kcrit = 1.0 (EN 1995-1-1 6.3.3(5))., the sentence the ambient timber check uses.
Timber fire uses the CEN values only: for any other design country the timber fire result reads Unavailable. A result with an Unavailable part, such as glulam lateral-torsional buckling, is shown as partial, never as a pass.
Concrete: tabulated data
A single span on two hinged supports uses Table 5.5. A beam with more than one span uses Table 5.6, because Statiko does not redistribute moments. A cantilever, or a single span with a fixed end, reads Unavailable. The check compares the beam width b with bmin, the smallest width of the row (column 2), and the axis distance a with amin, for the required resistance. amin is read from the column your width reaches; the check detail names it in the row Column for the axis distance.
| Table 5.5 | bmin / amin (mm), columns 2 to 5 | |||
|---|---|---|---|---|
| R30 | 80 / 25 | 120 / 20 | 160 / 15 | 200 / 15 |
| R60 | 120 / 40 | 160 / 35 | 200 / 30 | 300 / 25 |
| R90 | 150 / 55 | 200 / 45 | 300 / 40 | 400 / 35 |
| R120 | 200 / 65 | 240 / 60 | 300 / 55 | 500 / 50 |
| R180 | 240 / 80 | 300 / 70 | 400 / 65 | 600 / 60 |
| R240 | 280 / 90 | 350 / 80 | 500 / 75 | 700 / 70 |
Source: EN 1992-1-2 5.6.2, Table 5.5; kernel eurocode/fire/concrete/ConcreteFireBeamTables.kt:6-14 (Table 5.6 at :16-24).
eurocode/fire/concrete/ConcreteFireTabulatedBeam.kt:12-36amin is interpolated linearly between columns (5.2(12)). Custom minutes use the next table row at or above; above R240 the check reads Unavailable. Each bar must also meet the R30 value for its width (single layer) or half the average (several layers), as 5.2(17) requires. The tables hold for three-sided exposure at the reference load level ηfi = 0.7 (5.2(3)), for the Eurocode design country only. Four-sided exposure, other design countries, circular sections, concrete above C50/60 and density above 2600 kg/m³ read Unavailable. A continuous beam at R90 and above that needs the top-reinforcement rule of 5.6.3(3), or Table 5.7 at R120 and above, reads Unavailable, never Pass. The 500 °C isotherm method is not available in this version.
What you see
Fire results appear in the window's Fire verification group and in the report. With fire input, steel, timber, glulam and concrete beams also list Fire verification at the end of their checks column, marked as the fire design situation.
- Steel shows both methods side by side, then the steel fire verdict. The critical temperature method shows μ0, κ1, κ2, γM,fi with its provenance, θa,cr, Am/V, θa at the required time and the margin. The resistance method shows Mfi,t,Rd, Vfi,t,Rd and Mb,fi,t,Rd with χLT,fi.
- Timber shows kmod,fi, dchar,n, def, bfi, hfi, the charring phase, fm,d,fi and fv,d,fi, the bending and shear ratios, and σm,crit, λrel,m and kcrit.
- Concrete shows b, bmin, a, amin, the table, row and column, and the verdict.
Every fire result is Available, Unavailable with its reason, Invalid input, or Calculation failed. It is never a faked pass.
Source: spec/beam/fire.md rules 18, 33, 35, 38, 42, 43, 46 and 50.